H50S-RR

$0.00

The H50S-RR is a high-top, cast-in fire collar for concrete slabs.

Approved for Stack applications only.

For use with a range of pipe types and diameters (See below: click on a Report No. to access PDF).

Has an internal rubber ring that seals against the pipe.

Click Here for Installation Instructions

Click Here for Drawing

Download Revit file here

Clear
SKU: N/A Categories: ,

Documentation

Stack ApplicationsDia.FRLReport No.
120mm+ Concrete Slab
PVC Pipe
40
-/120/120
FSP2008
PVC Pipe50-/240/120FSP2016
HDPE Pipe40-/120/120FSP2028
Valsir Triplus Pipe40, 50-/240/120FSP2016
150mm+ Concrete Slab
PVC Pipe
40, 50
-/240/240FSP1575
- w Fitting Inside Collar50-/240/240FAR3932
- w Fitting Inside Collar40-/240/240FSP1577
P-PVC Pipe
32-/240/240FR5670
HDPE Pipe56
-/240/240FP4640
HDPE Pipe50-/240/240FSP1615
HDPE Pipe40-/240/240FSP1736
PEX-a Pipe
16, 20-/240/240FR5670
PEX-b Pipe
16, 20-/240/240FR5670
Rehau Raupiano Pipe 50-/240/180FAR4019
Rehau Raupiano Pipe40-/240/240FSP1564
- w Fitting Inside Collar40, 50-/240/240FSP1614
Valsir Triplus Pipe40, 50-/240/240FSP1652
Akatherm dBlue Pipe40, 50-/240/240
FSP1648
PEX-a Pipe32-/240/180
FSP2072
Side of Concrete Beam
PVC Pipe w Fitting Inside Collar
50-/240/240FRT190069

If the Slab Thickness is Increased to 180mm the FRL Increases to -/240/240

See Page 7 of FAR4019: Equivalence of H50S-RR and L50S & L40S Collars

Tested in Accordance with AS1530.4 & AS4072.1

NCC Compliant for the Above Uses

Print Friendly, PDF & Email

Product Specs

Element

,

Cast-in or Retrofit

Application

Pipe Type

, , , , , , ,