MS70R

The MS70R is a metal, retrofit fire collar for fire-rated plasterboard, concrete and masonry walls.

Tested and Assessed systems include electrical power cables, insulated copper pipes, as well as data & optical fibre cables.  (See below: click on a highlighted report no. to open report).

N.B. All Fire Resistance Levels (FRLs) achieved on framed plasterboard wall systems are applicable to concrete or masonry walls of equal or greater thickness (AS1530.4: 2014 Section 10.12.2 (c)).

Click Here for Installation Instructions

Click Here for Drawing

Download Revit file here

Click Here for Recommended Fixings Guide

Documentation

Summary of Conclusion Tables 8 & 9 (Pages 11 & 12) from CSIRO Assessment FCO3397  (click on highlighted report no. to open report).

The systems in Table 1 & Table 2 achieve the FRLs listed by wall type in Table 3 below:

Table 1: Lagged Pipe Details – Walls

ServicePipe (Min - Max)Lagging (Min - Max)Fire-rated Sealant ††
Copper Pair Coil1/4in & 3/8in
to 3/8in & 3/4in
9mm-15mm PE Foam Lagging or 9mm-25mm E-Flex Lagging or 25mm Foil Faced Sekisui LaggingAnnular gap between wall and services 10mm deep
Lagged Copper & Steel Pipes1/4in to 3/4in9mm-15mm PE Foam Lagging or 9mm-25mm E-Flex Lagging or 25mm Foil Faced Sekisui LaggingOptional
1in19mm-25mm E-Flex Lagging or 25mm Foil Faced Sekisui LaggingOptional
PN12 PVC Pipe15mm to 32mm19mm-25mm E-Flex Lagging or 25mm Foil Faced Sekisui LaggingOptional
Mixed ServicesVariousVariousAnnular gap between wall and services 10mm deep

Table 2: Conduit & Cable Details – Walls

ServiceMin to Max DetailFire-rated Sealant ††
PVC Conduit
Light to Medium Duty
20mm – 50mm PVC Conduit (empty to full of power cables, data and comms cables and fibre optic cables)Optional
Fibre Optic Cables
12F NBN Fibre Optic Cable
Collar empty to 100% fullOptional
Data and Comms Cables
Cat5e, Cat6, Cat7, RG-6
Collar empty to 100% fullOptional
Power Cables
Max 16mm² 3C+E Cables
Max 16mm² Single Conductor
Collar empty to 100% fullAnnular gap between wall and services 10mm deep
Mixed ServicesVariousVariousAnnular gap between wall and services 10mm deep

Table 3 FRL of MS70R on Walls

Wall TypesService in MS70R Collar
Copper Pair Coil
Lagged Copper and Steel Pipes
PVC Conduit
Fibre Optic Cables
Data and Comms Cables
Power Cables
Mixed Services Bundle or Collars Installed Flange to Flange
Plasterboard, Concrete and Masonry Walls
90mm+ P'board *
-/60/60
-/60/60
96mm+ P'board **
-/90/60
-/90/90
-/90/60
116mm+ P'board ***
-/120/120
-/120/120
128mm+ P'board ****
-/120/120
-/180/120
-/180/180
-/120/120
AAC Wall Systems
75mm Hebel PowerPanel (90min)
-/90/90
-/90/90
75mm Hebel PowerPanel (120min)
-/120/90
-/120/120
-/120/90
-/120/90
78mm SpeedPanel w/ 13mm PB patch
-/120/90
-/120/120
-/120/90
-/120/90
Framed MgO Wall Systems
MgO Board Wall *****
-/90/60
-/90/90
-/90/60

Table 4: Lagged Pipe Details – Slabs

FR LaggingLagging ThicknessServiceFire-rated Sealant ††
K-Flex, SuperMax or Armaflex FR Lagging9mm to 25mmCopper Pair Coil (1/4in&3/8in to 3/8in&3/4in)
Gap <5mm: Sealant Optional
Gap >5mm: Annular gap between slab and services, 10mm deep
19mm to 25mmLagged Copper/Steel Pipe (1/4in to 3/4in)
Lagged Copper/Steel Pipes (Up to 1in)
16-32mm PN12 PVCOptional
Foil Faced Sekisui Foam Lagging25mmCopper Pair Coil (1/4in&3/8in to 3/8in&3/4in)
Gap <5mm: Sealant Optional
Gap >5mm: Annular gap between slab and services, 10mm deep
Lagged Copper/Steel Pipe (1/4in to 3/4in)
Lagged Copper/Steel Pipes (Up to 1in)
16-32mm PN12 PVCOptional

Table 5: Conduit & Cable Details – Slabs

ServiceMin to Max DetailFire-rated Sealant ††
PVC Conduit
Light to Medium Duty
20mm – 50mm PVC Conduit (empty to full of power cables, data and comms cables and fibre optic cables)Optional
PVC Conduit 100mm Above & Below the Slab
Light to Medium Duty
20mm – 50mm PVC Conduit (empty to full of power cables, data and comms cables and fibre optic cables)Optional
Fibre Optic Cables
6F, 12F NBN Fibre Optic Cable
Up to 20 12F & 10 6F CablesGap <5mm: Sealant Optional
Gap >5mm: Annular gap between slab and services, 10mm deep
Data and Comms Cables
Cat5e
Up to 100 CablesGap <5mm: Sealant Optional
Gap >5mm: Annular gap between slab and services, 10mm deep
Data and Comms Cables
Cat6, Cat7, RG-6
Up to 60 CablesGap <5mm: Sealant Optional
Gap >5mm: Annular gap between slab and services, 10mm deep
Power Cables in Conduit
Max 16mm² 3C+E Cables
Max 16mm² Single Conductor
Up to 2 x 16mm² 3C+E Cables
Up to 2 x 16mm² Single Conductor
Optional

Table 6 FRL of MS70R on Slabs – Lagged Pipes

Lagged Pipes As Per Table 4Service in MS70R Collar
E-Flex Lagging
SuperMax Lagging
Armaflex Lagging
Foil Faced Sekisui Foam Lagging
Copper Pair Coil
-/180/120
-/180/90
-/180/90
-/180/90
Lagged Copper/Steel Pipe (1/4in to 3/4in)
-/180/120
-/180/180
Lagged Copper/Steel Pipes (Up to 1in)
-/180/90
PN12 PVC Pipes
-/180/180

Table 7 FRL of MS70R on Slabs – Conduit & Cables

Service in MS70R Collar
PVC Conduit
Fibre Optic Cables
Data & Comms Cables
Power Cables in Conduit
150mm+ Concrete Slab
-/180/180
-/180/120
-/180/180
180mm+ Concrete Slab
-/240/240
-/240/120
-/240/180

* 1 x 13mm Fire-rated Plasterboard Sheets Either side of a 64mm Steel Stud.

** 1 x 16mm Fire-rated Plasterboard Sheets Either side of a 64mm Steel Stud.

*** 2 x 13mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud

**** 2 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud

***** 1 x 10mm FireCrunch MgO Board or 2 x 7.5mm Multiboard MgO Board Either Side of 90mm Steel Stud Contact Manufacturer for Wall System Details

N.B. All Fire Resistance Levels (FRLs) achieved on framed plasterboard wall systems are applicable to concrete or masonry walls of equal or greater thickness (AS1530.4: 2014 Section 10.12.2 (c)).

Sealant requirement for the purposes of Fire Rating only – Fullers Firesound used in tests

Tested in Accordance with AS1530.4 & AS4072.1

NCC 2022 Compliant for the Above Uses

Print Friendly, PDF & Email

Product Specs

Element

, , , , , ,

Cast-In or Retrofit

Application

,

Pipe Type

, , , , , , ,

Tested Systems

ServiceSealantFRLReport No.
150mm+ Concrete Slab
3/8in & 3/4in Copper Pair Coil Bundle w/
10mm Non-F/R Lagging (PE Foam), 2.5mm² 3C+E Round Power Cable and 25mm Pressure PVC
Annular gap between slab and services 10mm deep-/120/120FSP2049
Power Cable Bundle in Short Conduit w/ 60mm Conduit 100mm above & Below slab, 3x6mm² 3C+E Power Cables
3x16mm² 3C+E Power Cables
Annular gap between wall and services 10mm deep-/240/180FSP2174
Power Cable Bundle in Conduit w/ 60mm Conduit, 3x6mm² 3C+E Power Cables 3x16mm² 3C+E Power Cables Annular gap between wall and services 10mm deep-/240/180FSP2174
1in Copper Pipe w/ 19mm F/R Lagging (F/R E-Flex) and 2.5mm² 3C TPS Flat Power Cable None-/240/120FSP2225
3/4in Copper Pipe w/ 9mm F/R Lagging (F/R Armaflex) and 2.5mm² 3C TPS Flat Power Cable None-/240/180FSP2231
32mm PN12 PVC Pipe w/ 19mm F/R Lagging (F/R Armaflex)None-/240/180FSP2225
50mm Medium Duty Conduit w/
2x16mm² 3C+E Power Cables
2x6mm² 3C+E Power Cables
None-/240/180FSP2135
20xCat5e Data CablesNone-/240/180FSP2135
100xCat5e Data CablesNone-/240/180FSP2135
60xCat7 Data CablesNone-/240/120FSP2225
Optic Fibre Cables w/
20x12F Fibre Optic Cables
10x6F Fibre Optic Cables
None-/240/180FSP2203
90mm+ Plasterboard Wall *
3/8in & 3/4in Copper Pair Coil Bundle w/
9mm Non-F/R Lagging (PE Foam), 2.5mm² 3C+E Round Power Cable and 25mm Pressure PVC
Annular gap between wall and services 10mm deep-/60/60FSP2120
Power Cable Bundle w/ 3x6mm² 3C+E Power Cables
6x16mm² 3C+E Power Cables
Annular gap between wall and services 10mm deep-/60/60FSP2120
1in Copper Pipe w/ 19mm F/R Lagging (F/R Armaflex) and 2.5mm² 3C TPS Flat Power Cable None-/60/60FSP2120
1in Copper Pipe w/ 25mm Foil Faced Lagging None-/60/60FSP2188
32mm PN12 PVC Pipe w/ 19mm F/R Lagging (F/R Armaflex) None-/60/60FSP2216
50mm Medium Duty Conduit w/
2x16mm² 3C+E Power Cables
2x6mm² 3C+E Power Cables
None-/60/60FSP2120
20xCat5e Data CablesNone-/60/60FSP2120
100xCat5e Data CablesNone-/60/60FSP2120
116mm+ Plasterboard Wall **
3/8in & 3/4in Copper Pair Coil Bundle w/ 10mm Non-F/R Lagging (PE Foam), 2.5mm² 3C+E Round Power Cable and 25mm Pressure PVCAnnular gap between wall and services 10mm deep-/120/120FSP2126
Power Cable Bundle w/ 3x6mm² 3C+E Power Cables
6x16mm² 3C+E Power Cables
Annular gap between wall and services 10mm deep-/120/120FSP2126
1in Copper Pipe w/
19mm F/R Lagging (F/R Armaflex) and 2.5mm² 3C TPS Flat Power Cable
None-/120/120FSP2126
32mm PN12 PVC Pipe w/ 19mm F/R Lagging (F/R Armaflex) None-/120/120FSP2206
50mm Medium Duty Conduit w/
2x16mm² 3C+E Power Cables
2x6mm² 3C+E Power Cables
None-/120/120FSP2126
20xCat5e Data CablesNone-/120/120FSP2126
100xCat5e Data CablesNone-/120/120FSP2126
75mm+ Hebel Powerpanel Wall (90min)
3/8in & 3/4in Copper Pair Coil Bundle w/ 10mm Non-F/R Lagging (PE Foam), 2.5mm² 3C+E Round Power Cable and 25mm Pressure PVCAnnular gap between wall and services 10mm deep-/90/90FSP2058
Power Cable Bundle w/ 3x6mm² 3C+E Power Cables
6x16mm² 3C+E Power Cables
None-/90/90FSP2118
1in Copper Pipe w/
19mm F/R Lagging (F/R Armaflex) and 2.5mm² 3C TPS Flat Power Cable
None-/90/90FSP2118
50mm Medium Duty Conduit w/
2x6mm² 3C+E power cables
2x16mm² 3C+E power cables
None-/90/90FSP2118
20xCat5e Data CablesNone-/90/90FSP2118
100xCat5e Data CablesNone-/90/90FSP2118
50mm PN6 PVC PipeNone-/90/90FSP2118

* 1 x 13mm Fire-rated Plasterboard Sheets Either side of a 64mm Steel Stud.

** 2 x 13mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud

Tested in Accordance with AS1530.4 & AS4072.1

NCC Compliant for the Above Uses

Print Friendly, PDF & Email

Purchase Information

Please contact your local distributor for purchase enquiries. Contact us here.

QLD

Drillfast
Drillfast
www.drillfast.com.au
Email: sales@drillfast.com.au
Phone: 1300 923 414



Fyreguard
www.fyreguard.com
Brisbane Phone: (07) 3865 4422
Gold Coast Phone: (07) 5593 4955



Global Fasteners www.global-fasteners.com.au

Townsville Phone: (07) 4727 1111
Cairns Phone: (07) 4035 3367
Mackay Phone: (07) 4957 8855
Rockhampton Phone: (07) 4921 0800


VIC


Drillcut
www.drillcut.com.au
Email: sales@drillcut.com.au
Phone: (03) 8301 9999


ACT

Powagroup
Powagroup
: www.powagroup.com.au
Email: sales@powagroup.com.au
Phone: 1300 303 366

Print Friendly, PDF & Email