Summary of Conclusion Tables 8 & 9 (Pages 11 & 12) from CSIRO Assessment FCO3397 (click on highlighted report no. to open report).
The systems in Table 1 & Table 2 achieve the FRLs listed by wall type in Table 3 below:
Table 1
Service | Pipe (Min - Max) | Lagging (Min - Max) | Fire-rated Sealant †† |
---|---|---|---|
Copper Pair Coil | 1/4in & 3/8in to 3/8in & 3/4in | 9mm-15mm PE Foam Lagging or 9mm-25mm F/R Lagging | Annular gap between wall and services 10mm deep |
Lagged Copper & Steel Pipes | 1/4in to 3/4in | 9mm-15mm PE Foam Lagging or 9mm-25mm F/R Lagging | Optional |
1in | 19mm-25mm F/R Lagging | Optional |
Table 2
Service | Min to Max Detail | Fire-rated Sealant †† | |
---|---|---|---|
PVC Conduit Light to Medium Duty | 20mm – 50mm PVC Conduit (empty to full of power cables, data and comms cables and fibre optic cables) | Optional | |
Fibre Optic Cables 12F NBN Fibre Optic Cable | Collar empty to 100% full | Optional | |
Data and Comms Cables Cat5e, Cat6, Cat7, Cat8, RG-6 | Collar empty to 100% full | Optional | |
Power Cables Max 16mm² 3C+E Cables Max 16mm² Single Conductor | Collar empty to 100% full | Annular gap between wall and services 10mm deep |
Table 3
Wall Types | Service in MS70R Collar | ||||||
---|---|---|---|---|---|---|---|
Copper Pair Coil | Lagged Copper and Steel Pipes | PVC Conduit | Fibre Optic Cables | Data and Comms Cables | Power Cables | Mixed Services Bundle or Collars Installed Flange to Flange |
|
Plasterboard, Concrete and Masonry Walls † |
|||||||
90mm+ P'board * | -/60/60 | -/60/60 |
|||||
96mm+ P'board ** | -/90/60 | -/90/90 | -/90/60 |
||||
116mm+ P'board *** | -/120/120 | -/120/120 |
|||||
128mm+ P'board **** | -/120/120 | -/180/120 | -/180/180 | -/120/120 |
|||
AAC Wall Systems |
|||||||
75mm Hebel PowerPanel (90min) | -/90/90 | -/90/90 |
|||||
75mm Hebel PowerPanel (120min) | -/120/90 | -/120/120 | -/120/90 | -/120/90 |
|||
78mm SpeedPanel w/ 13mm PB patch | -/120/90 | -/120/120 | -/120/90 | -/120/90 |
|||
Framed MgO Wall Systems |
|||||||
MgO Board Wall ***** | -/90/60 | -/90/90 | -/90/60 |
* 1 x 13mm Fire-rated Plasterboard Sheets Either side of a 64mm Steel Stud.
** 1 x 16mm Fire-rated Plasterboard Sheets Either side of a 64mm Steel Stud.
*** 2 x 13mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud
**** 2 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud
***** 1 x 10mm FireCrunch MgO Board or 2 x 7.5mm Multiboard MgO Board Either Side of 90mm Steel Stud Contact Manufacturer for Wall System Details
† N.B. All Fire Resistance Levels (FRLs) achieved on framed plasterboard wall systems are applicable to concrete or masonry walls of equal or greater thickness (AS1530.4: 2014 Section 10.12.2 (c)).
†† Sealant requirement for the purposes of Fire Rating only – Fullers Firesound used in tests
Tested in Accordance with AS1530.4 & AS4072.1
NCC Compliant for the Above Uses