Documentation
Stack Applications | Dia. | FRL | Report No. |
150mm+ Concrete Slab | |||
PVC Pipe †† | 65 | -/240/180 | FAR3933 |
PVC Pipe | 50 | -/240/240 | FP4640 |
- w Fitting Inside Collar | 50 | -/240/240 | FP4640 |
HDPE Pipe †† | 50, 56, 63 | -/240/180 | FAR3933 |
+GF+ George Fischer Progef Pipe | 63 | -/240/240 | FSP1657 |
Wall Applications | Dia. | FRL | Report No. |
128mm+ Plasterboard Wall * | |||
PVC Pipe | 65 | -/180/120 | FAR3929 |
PVC Pipe | 50 | -/180/120 | FP4874 |
- w Fitting Inside Collar | 50 | -/180/120 | FAR3929 |
HDPE Pipe | 50, 56, 63 | -/180/120 | FAR3929 |
PP-R sdr 7.4 Pipe ††† | 20, 63 | -/180/180 | FSP1360 |
PP-R sdr 7.4 Pipe | 25, 32, 40, 50 | -/180/180 | FAR3929 |
PE sdr 7.4 Pipe ††† | 20, 63 | --/180/180 | FSP1366 |
PE sdr 7.4 Pipe | 25, 32, 40, 50 | --/180/180 | FAR3929 |
+GF+ George Fischer Progef Pipe | 63 | -/180/180 | FSP1658 |
96mm+ Plasterboard Wall ** | |||
PVC Pipe | 65 | -/90/60 | FP5663 |
HDPE Pipe | 50, 56, 63 | -/90/60 | FC10395 |
FireCruch MgO Board Wall † | |||
PVC Pipe | 50, 65 | -/90/90 | FCO3268 |
- w Fitting Inside Collar | 50 | -/90/90 | FCO3268 |
HDPE Pipe | 50, 56, 63 | -/90/90 | FCO3268 |
PP-R sdr 7.4 Pipe | 20, 25, 32, 40, 50, 63 | -/90/90 | FCO3268 |
PE sdr 7.4 Pipe | 20, 25, 32, 40, 50, 63 | -/90/90 | FCO3268 |
+GF+ George Fischer Progef Pipe | 63 | -/90/90 | FCO3268 |
* 2 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud
** 1 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud
† 1 x 10mm Firecrunch MgO Board Either Side of 90mm Steel Stud. Contact Manufacturer for Wall System Details
†† If the Slab Thickness is Increased to 180mm the FRL Increases to -/240/240
††† Refer to FCO3379 for -/180/180
Tested in Accordance with AS1530.4 & AS4072.1
NCC Compliant for the Above Uses