Floorwaste and Shower Applications | Dia. | FRL | Report No. |
120mm+ Concrete Slab | |||
PVC (SC) Pipe | 100 | -/120/120 | FSP2008 |
150mm+ Concrete Slab |
|||
PVC (SC) Pipe | 100 | -/240/240 | FSP1576 |
- w Fitting Inside Collar | 100 | -/240/240 | FSP1577 |
PVC Pipe | 100 | -/240/240 | FAR3932 |
PVC Pipe | 80** | -/240/240 | FSP1576 |
PVC Pipe | 65* | -/240/240 | FSP1577 |
PVC Pipe | 50* | -/240/240 | FP4640 |
- w Fitting Inside Collar | 50*, 65*, 80**, 100 | -/240/240 | FAR3932 |
HDPE Pipe | 110 | -/240/240 | FSP1592 |
HDPE Pipe | 63*, 75**, 90 | -/240/240 | FAR3932 |
HDPE (Silent) Pipe | 110 | -/240/240 | FAR3932 |
Rehau Raupiano Pipe | 110 | -/240/240 | FSP1564 |
Rehau Raupiano Pipe | 75**, 90 | -/240/240 | FC12806 |
Valsir Triplus Pipe | 110 | -/240/240 | FSP1652 |
Akatherm dBlue Pipe *** | 110 | -/240/240 | FSP1648 |
Side of Concrete Beam | |||
PVC (SC) Pipe w Fitting Inside Collar | 100 | -/240/240 | FSP1715 |
Stack Applications | Dia. | FRL | Report No. |
150mm+ Concrete Slab | |||
PP-R sdr 7.4 Pipe | 110 | -/240/240 | FSP1359 |
PP-R sdr 7.4 Pipe | 63*, 75**, 90 | -/240/180 | FAR3932 |
PP-R sdr 7.4 Pipe | 50* | -/240/180 | FSP1359 |
PE sdr 7.4 Pipe | 110 | -/240/180 | FSP1367 |
PE sdr 7.4 Pipe | 63*, 75**, 90 | -/240/180 | FAR3932 |
PE sdr 7.4 Pipe | 50* | -/240/240 | FSP1367 |
Rehau Raupiano Pipe w Fitting Inside Collar | 75** | -/240/240 | FSP1614 |
+GF+ Coolfit 2.0 Pipe | d63/110 | -/240/240 | FSP1891 |
* For best fit, use the L100FWS with 65 Reducer Ring
** For best fit, use the L100FWS with 80 Reducer Ring
*** Ask Pipe Manufacturer for Installation Instructions
See Page 7 of FAR4019: Equivalence of L100FWS and L65FWS, L80FWS & H100FWS-RR Collars
Tested in Accordance with AS1530.4 & AS4072.1
NCC Compliant for the Above Uses