Documentation
Floorwaste and Shower Applications | Dia. | FRL | Report No. |
PVC (SC) Pipe | 100 | -/240/240 | FSP1576 |
– w Fitting Inside Collar | 100 | -/240/240 | FSP1577 |
PVC Pipe | 100 | -/240/240 | FAR3932 |
PVC Pipe | 80 | -/240/240 | FSP1576 |
PVC Pipe | 65 | -/240/240 | FSP1577 |
PVC Pipe | 50 | -/240/240 | FP4640 |
– w Fitting Inside Collar | 50, 65, 80, 100 | -/240/240 | FAR3932 |
HDPE Pipe | 100 | -/240/240 | FSP1592 |
HDPE Pipe | 63, 75, 90 | -/240/240 | FAR3932 |
HDPE (Silent) Pipe | 100 | -/240/240 | FAR3932 |
Rehau Raupiano Pipe | 100 | -/240/240 | FSP1564 |
Valsir Triplus | 110 | -/240/240 | FSP1652 |
Akatherm dBlue* | 110 | -/240/- | FSP1648 |
Stack Applications | |||
PP-R sdr 7.4 Pipe | 110 | -/240/240 | FSP1359 |
PP-R sdr 7.4 Pipe | 63, 75, 90 | -/240/180 | FAR3932 |
PP-R sdr 7.4 Pipe | 50 | -/240/180 | FSP1359 |
PE sdr 7.4 Pipe | 110 | -/240/180 | FSP1367 |
PE sdr 7.4 Pipe | 63, 75, 90 | -/240/180 | FAR3932 |
PE sdr 7.4 Pipe | 50 | -/240/240 | FSP1367 |
Rehau Raupiano Pipe with Fitting Inside Collar | 75 | -/240/240 | FSP1614 |
+GF+ Coolfit 2.0 Pipe | d63/110 | -/240/240 | FSP1891 |
*Ask Pipe Manufacturer for Installation Instructions
See Page 7 of FAR4019: Equivalence of H100FWS-RR and L65FWS, L80FWS & L100FWS Collars
Tested in Accordance with AS1530.4 & AS4072.1
BCA Compliant for the Above Uses.