Documentation
| Floorwaste and Shower Applications | Dia. | FRL | Report No. |
| 120mm+ Concrete Slab | |||
| PVC (SC) Pipe | 100 | -/120/120 | FSP2008 |
| 150mm+ Concrete Slab |
|||
| PVC (SC) Pipe | 100 | -/240/240 | FCO3426 |
| - w Fitting Inside Collar | 100 | -/240/240 | FCO3426 |
| PVC Pipe | 50*, 65*, 80**, 100 | -/240/240 | FCO3426 |
| - w Fitting Inside Collar | 50*, 65*, 80**, 100 | -/240/240 | FCO3426 |
| HDPE Pipe | 110 | -/240/240 | FCO3426 |
| HDPE Pipe | 63*, 75**, 90 | -/240/240 | FAR3932 |
| HDPE (Silent) Pipe | 110 | -/240/240 | FAR3932 |
| Rehau Raupiano Pipe | 110 | -/240/240 | FCO3426 |
| Rehau Raupiano Pipe | 75**, 90 | -/240/240 | FC12806 |
| Valsir Triplus Pipe | 110 | -/240/240 | FSP1652 |
| Akatherm dBlue Pipe *** | 110 | -/240/0 | FSP1648 |
| Side of Concrete Beam | |||
| PVC (SC) Pipe w Fitting Inside Collar | 100 | -/240/240 | FCO3426 |
| Stack Applications | Dia. | FRL | Report No. |
| 150mm+ Concrete Slab | |||
| PP-R sdr 7.4 Pipe | 50*, 63*, 75**, 90, 110 | -/180/180 | FCO3426 |
| PE sdr 7.4 Pipe | 50*, 63*, 75**, 90, 110 | -/180/180 | FCO3426 |
| Rehau Raupiano Pipe w Fitting Inside Collar | 75** | -/240/240 | FSP1614 † |
| +GF+ Coolfit 2.0 Pipe | d63/110 | -/240/240 | FSP1891 |
* For best fit, use the L100FWS with 65 Reducer Ring
** For best fit, use the L100FWS with 80 Reducer Ring
*** Ask Pipe Manufacturer for Installation Instructions
† Refer to report in conjunction with FCO3407
See Page 8 & 9 of FAR3932: Equivalence of L100FWS and L65FWS, L80FWS & H100FWS-RR Collars
Tested in Accordance with AS1530.4 & AS4072.1
NCC 2022 Compliant for the Above Uses