Documentation
| Floorwaste and Shower Applications | Dia. | FRL | Report No. |
| 120mm+ Concrete Slab | |||
| Valsir Triplus Pipe | 110 | -/120/120 | FSP2049 |
| 150mm+ Concrete Slab | |||
| PVC Pipe | 150 | -/240/240 | FCO3426 |
| - w Fitting Inside Collar | 150 | -/240/240 | FCO3426 |
| PVC (SC) Pipe | 100 | -/240/240 | FCO3426 |
| - w Fitting Inside Collar | 100 | -/240/240 | FCO3426 |
| Stack Applications | Dia. | FRL | Report No. |
| 150mm+ Concrete Slab | |||
| PVC Pipe | 150 | -/240/240 | FCO3426 |
| - w Fitting Inside Collar | 150 | -/240/240 | FCO3426 |
| PVC (SC) Pipe | 100 | -/240/240 | FAR3932 |
| - w Fitting Inside Collar | 100 | -/240/240 | FAR3932 |
| HDPE Pipe | 160 | -/180/180 | FAR3932* |
| HDPE Pipe | 125 | -/240/240 | FCO3426 |
| PP-R sdr 7.4 Pipe | 160 | -/240/180 | FAR3932* |
| PE sdr 7.4 Pipe | 160 | -/240/120 | FAR3932** |
| Rehau Raupiano Pipe | 110, 160 | -/240/240 | FCO3426 |
| - w Fitting Inside Collar | 110 | -/240/240 | FCO3426 |
| Valsir Triplus Pipe | 160 | -/180/180 | FCO3426 |
| Akatherm dBlue Pipe | 160 | -/240/120 | FCO3426 |
* 180mm+ Thick Concrete Slab
** FRL of -/240/180 When Installed Into a 180mm+ Concrete Slab
Tested in Accordance with AS1530.4 & AS4072.1
NCC 2022 Compliant for the Above Uses.