Documentation
| Stack Applications | Dia. | FRL | Report No. |
| 120mm+ Concrete Slab | |||
| PVC (SC) Pipe | 100 | -/240/120 | FSP2016 |
| - w Fitting Inside Collar | 100 | -/240/120 | FSP2177 |
| PVC Pipe | 80 | -/240/120 | FSP2177 |
| PVC Pipe | 50 | -/240/120 | FSP2002 |
| P-PVC Pipe | 80, 100 | -/240/120 | FSP2116 |
| HDPE Pipe | 110 | -/120/120 | FSP2028 |
| Valsir Triplus Pipe | 75, 110 | -/120/120 | FSP2008 |
| Unused Collar Plug | 100 | -/180/120 | FSP2153 |
| 150mm+ Concrete Slab |
|||
| PVC (SC) Pipe | 100 | -/240/240 | FCO3426 |
| - w Fitting Inside Collar | 100 | -/240/240 | FCO3426 |
| PVC Pipe | 65, 80, 90, 100 | -/240/240 | FCO3426 |
| - w Fitting Inside Collar | 65, 80, 90, 100 | -/240/240 | FCO3426 |
| Fastflow PVC Pipe | 75, 100 | -/240/180 | FCO3426 |
| HDPE Pipe * | 110 | -/240/240 | FCO3426 |
| HDPE Pipe | 63, 75, 90 | -/240/240 | FAR3932 |
| HDPE (Silent) Pipe | 110 | -/240/240 | FAR3932 |
| Rehau Raupiano Pipe | 75, 90, 110 | -/240/240 | FC12806 |
| - w Fitting Inside Collar | 75, 90, 110 | -/240/240 | FC12806 |
| Valsir Triplus Pipe | 75, 110 | -/240/240 | FCO3426 |
| - w Fitting Inside Collar | 90 | -/240/180 | FSP2224 |
| - w Fitting Inside Collar | 75 | -/240/180 | FCO3426 |
| Akatherm dBlue Pipe | 75, 110 | -/240/240 | FCO3426 |
| Wavin Astolan Pipe | 70, 110 | -/240/240 | FSP1771 |
| Fuseal PP110 Pipe | 110 | -/240/180 | FSP2274 |
| Side of Concrete Beam | |||
| PVC (SC) Pipe | 100 | -/240/240 | FCO3426 |
* Can be Used With a Geberit SuperTube BottomTurn Bend Inside the Collar for an FRL of -/240/180. Refer to FSP2116 Pentration 4
See Page 8 & 9 of FAR3932: Equivalence of H100S and L65S, L80S & L100S Collars
Tested in Accordance with AS1530.4 & AS4072.1
NCC 2022 Compliant for the Above Uses