Documentation
| Stack Applications | Dia. | FRL | Report No. |
| 150mm+ Concrete Slab | |||
| PVC Pipe | 50, 65 | -/240/240 | FAR3933 |
| - w Fitting Inside Collar | 50 | -/240/240 | FAR3933 |
| P-PVC Pipe | 50 | -/240/180 | FSP2315 |
| HDPE Pipe | 50, 56, 63 | -/240/240 | FAR3933 |
| +GF+ George Fischer Progef Pipe | 63 | -/240/240 | FSP1657 †† |
| Wall Applications | Dia. | FRL | Report No. |
| 128mm+ Plasterboard Wall * | |||
| PVC Pipe | 50, 65 | -/180/120 | FAR3929 |
| - w Fitting Inside Collar | 50 | -/180/120 | FAR3929 |
| HDPE Pipe | 50, 56, 63 | -/180/120 | FAR3929 |
| PP-R sdr 7.4 Pipe | 20, 25, 32, 40, 50, 63 | -/180/180 | FAR3929 |
| PE sdr 7.4 Pipe | 20, 25, 32, 40, 50, 63 | --/180/180 | FAR3929 |
| +GF+ George Fischer Progef Pipe | 63 | -/180/180 | FSP1658 †† |
| 96mm+ Plasterboard Wall ** | |||
| PVC Pipe | 65 | -/90/60 | FC10395 |
| HDPE Pipe | 50, 56, 63 | -/90/60 | FC10395 |
| FireCruch MgO Board Wall † | |||
| PVC Pipe | 50, 65 | -/90/90 | FCO3268 |
| - w Fitting Inside Collar | 50 | -/90/90 | FCO3268 |
| HDPE Pipe | 50, 56, 63 | -/90/90 | FCO3268 |
| PP-R sdr 7.4 Pipe | 20, 25, 32, 40, 50, 63 | -/90/90 | FCO3268 |
| PE sdr 7.4 Pipe | 20, 25, 32, 40, 50, 63 | -/90/90 | FCO3268 |
| +GF+ George Fischer Progef Pipe | 63 | -/90/90 | FCO3268 |
* 2 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud
** 1 x 16mm Fire-rated Plasterboard Sheets Either Side of 64mm Steel Stud
† 1 x 10mm Firecrunch MgO Board Either Side of 90mm Steel Stud. Contact Manufacturer for Wall System Details
†† Refer to report in conjunction with FCO3407
Tested in Accordance with AS1530.4 & AS4072.1
NCC 2022 Compliant for the Above Uses