Our Fire Collars

GAS 63

$0.00

The Snap Gas-63 is a metal, externally mounted collar, and is designed for both wall and floor applications.

For use on PX-AL-PX composite gas pipe (See below: click on a Report No. to access PDF).

N.B. All Fire Resistance Levels (FRLs) achieved on framed plasterboard wall systems are applicable to concrete and masonry walls of equal or greater thickness (AS1530.4: 2014 Section 10.12.2 (c)).

Click Here for Installation Instructions

Click Here for Drawing

Download Revit file here

Clear

Documentation

Mounted ApplicationDia.FRLReport No.
Rifeng PX-AL-PX (Floor)63-/240/240FSP1340
Valsir Pexal (Floor)63-/240/120FSP1758
Valsir Pexal (Wall)63-/180/60FSP1759*

*2 x 13mm Sheets of Fire Rated Plasterboard Either Side of 64mm Steel Stud

Tested in Accordance with AS1530.4-2005 & AS4072.1-2005

NCC Compliant for the Above Uses

Print Friendly, PDF & Email

Product Specs

Element

, ,

Cast-in or Retrofit

Floorwaste or Stack

, ,

Pipe Type

, ,

Choose Element here
Click arrows to expand selection