GAS 50

$0.00

The Snap Gas50 is a metal, cast-in or externally mounted collar, and is designed for both wall and floor applications.

For use on PX&PE/AL composite gas pipes.

Tested on a range of pipe types and diameters (See below: click on a Report No. to access PDF)

N.B. All Fire Resistance Levels (FRLs) achieved on framed plasterboard wall systems are applicable to concrete and masonry walls of equal or greater thickness (AS1530.4 Section 10.11.2 (b)).

Click Here for Floor Installation Instructions

Click Here for Wall Instalation Instructions

Click Here for Drawing

 

Clear
SKU: N/A Category:

Documentation

Mounted Application Dia. FRL Report No.
75mm+ Hebel Powerpanel
Pex-Al-Pex 50 -/120/60 FSP1807
Rehau PX-AL-PE
Rehau PX-AL-PE (Floor) 40 -/240/240 FSP1340
Rehau PX-AL-PE (Wall) 40 -/180/180 FSP1341
Rifeng PX-AL-PX
Rifeng* PX-AL-PX (Floor) 40, 50 -/240/240 FCO2719
Rifeng* PX-AL-PX (Floor) 32 -/240/240 FSP1339
Rifeng* PX-AL-PX (Plasterboard Wall**) 40, 50 -/180/120 FCO2719
Rifeng* PX-AL-PX (Plasterboard Wall**) 32 -/180/180 FSP1341
Rifeng* PX-AL-PX (Masonry & Concrete Wall) 32, 40, 50 -/180/120 FCO2719
Iplex PE-AL-PE
Iplex PE-Al-PE (Floor) 50 -/240/240 FSP1339
Iplex PE-AL-PE (Floor) 32, 40 -/240/240 FCO2718
Iplex PE-AL-PE (Plasterboard Wall**) 50 -/180/120 FSP1341
Iplex PE-AL-PE (Plasterboard Wall**) 32, 40 -/180/120 FCO2718
Iplex PE-AL-PE (Concrete & Masonry Wall) 32, 40, 50 -/180/120 FCO2718
Valsir Pexal
Valsir Pexal (Floor) 50 -/240/180 FSP1771
Valsir Pexal (Floor) 40 -/240/120 FSP1758
Valsir Pexal (Wall)*** 50 -/180/90 FSP1759
Valsir Pexal (Wall)*** 32, 40 -/180/120 FSP1759
Cast-In Application
Rehau PX-AL-PE 40 -/240/180 FSP1340
Rifeng* PX-AL-PX 50 -/240/180 FSP1340
Rifeng* PX-AL-PX 40 -/240/180 FCO2719
Rifeng* PX-AL-PX 32 -/240/240 FSP1340
Iplex PE-AL-PE 32 -/240/240 FSP1340

*Applies to Gaspex, Waterpex, Heatpex, & Chillpex

**2 x 16mm Fire-rated Sheets Either Side of 64mm Steel Stud

***2 x 13mm Fire-rated Sheets Either Side of 64mm Steel Stud

Tested in Accordance with AS1530.4-2005 & AS4072.1-2005 and later

BCA Compliant for the Above Uses 

Product Specs

Element

, , ,

Floorwaste or Stack

, ,

Cast-in or Retrofit

,

Pipe Type

, ,