GAS 32

$0.00

The Snap Gas 32 is a metal, externally mounted collar designed for both wall and floor applications.

For use on PX&PE/AL composite gas pipe.

Tested on a range of pipe brands and diameters. (See below: click on a Report No. to access PDF)

N.B. All Fire Resistance Levels (FRLs) achieved on framed plasterboard wall systems are applicable to concrete and masonry walls of equal or greater thickness (AS1530.4 Section 10.11.2 (b)).

Click Here for Floor Installation Instructions

Click Here for Wall Installation Instructions

Click Here for Drawings

Clear
SKU: N/A Category:

Documentation

Mounted Application Dia. FRL Report No.
Rehau PX-Al-PE
Rehau PX-AL-PE (Floor) 32 -/240/240 FSP1339
Rehau PX-AL-PE (Wall) 16 -/180/180 FSP1341
Rifeng PX-AL-PX
Rifeng* PX-AL-PX (Floor) 16, 32 -/240/240 FSP1339
RifengPX-AL-PX (Floor) 20, 25 -/240/240 FCO2719
Rifeng* PX-AL-PX (128mm+ Plasterboard Wall)** 16, 20, 25, 32 -/180/180 FCO2719
Rifeng* PX-AL-PX (Concrete & Masonry Wall) 16, 20, 25, 32 -/180/180 FCO2719
 Rifeng* PX-AL-PX (96mm+ Plasterboard Wall)***  20 -/90/60 FP5663
Iplex PE-AL-PE
Iplex PE-AL-PE (Floor) 16, 32 -/240/240 FSP1339
Iplex PE-AL-PE (Floor) 20, 25 -/240/240 FCO2718
Iplex PE-AL-PE (128mm+ Plasterboard Wall)** 32 -/180/120 FSP1341
Iplex PE-AL-PE (128mm+ Plasterboard Wall)** 16 -/180/180 FSP1341
Iplex PE-AL-PE (128mm+Plasterboard Wall)** 20, 25 -/180/180 FCO2718
Iplex PE-AL-PE (Concrete & Masonry Wall) 16, 20, 25, 32 -/180/180 FCO2718
Valsir Pexal
Valsir Pexal (Floor Slab) 15, 20, 26, 32 -/240/240 FSP1758
Valsir Pexal (Wall)**** 20, 26 -/180/120 FSP1759
Valsir Pexal (Wall)**** 15 -/180/180 FSP1759
75mm + Hebel Powerpanel
PX-AL-PX Pipe 20, 25, 32 -/120/120 FSP1822
PX-AL-PX Pipe 16 -/120/120 FSP1783

*Applies to Gaspex, Waterpex, Heatpex & Chillplex

**2 x 16mm Fire-rated Sheets Either Side of 64mm Steel Stud

***1 x 16mm Fire-rated Sheets Either Side of 64mm Steel Stud

****2 x 13mm Fire-rated Sheets Either Side of 64mm Steel Stud

Tested in Accordance with AS1530.4 & AS4072.1

BCA Compliant for the Above Uses

Product Specs

Element

, , , , ,

Cast-in or Retrofit

,

Floorwaste or Stack

, ,

Pipe Type

, , , ,